chexit alarm with no delayed egress

RELATED FAQS

Question
Answer
The Von Duprin Chexit device will not automatically rearm itself after a fire alarm clears.  After a Fire Alarm has triggered the Von Duprin Chexit device, the device must be manually reset&nb...
For Motor driven Chexit devices shipped from the factory after 8-24-2015, the Chexit Secure Relay Contacts( white and violet wires) change state to signal the device is not secure. Check the f...
For Solenoid driven Chexit devices shipped from the factory prior to 8-24-2015, the following could cause the device not to provide delay egress:Measure the voltage between green and orange wires o...
There is no conversion kit for Von Duprin Chexit device.  If delayed egress Chexit device is required, the entire device must be replaced.
The CX (Chexit) is the delayed egress option for the 98/99 series or 33/35A rim device. The device will create a 15 second delay with audible alarm when an unauthorized person tries to ex...
You can not use these options together on the same device per the following reasons: QEL/EL device retracts the latch bolt of the exit device allowing entry. CX (Chexit) device locks the p...
Chexit devices shipped prior to 8-24-2015 with solenoid driven could cause the Von Duprin CX solenoid to pull and drop and sound the alarm with solid LED or no LED light after the rear...
The release delay time for the Chexit is programmed into the Chexit module and cannot be changed in the field. The Chexit module would need to be replaced to reduce the release time of the Che...