Chexit flashes red when armed

RELATED FAQS

Question
Answer
Most common issue listed below: Chexit devices shipped after 8-24-2015 with motor driven. The Green wire is not shoeted to the Red wire if no Access Control system is used.If Access Control is us...
 Chexit devices shipped prior to 8-24-2015 with solenoid driven. The GREEN wire is not shorted to the WHITE if no Access Control system is used.If Access Control system is used,...
Chexit devices shipped prior to 8-24-2015 with solenoid driven could cause the Von Duprin CX solenoid to pull and drop and sound the alarm with solid LED or no LED light after the rear...
Followings could cause the Chexit device to go into alarm after the rearm time: Chexit devices shipped after 8-24-2015 with motor driven: Module DPS LED is ON DPS switch contact is open: Close t...
Chexit devices shipped prior to 8-24-2015 with solenoid driven: Chexit device has a RX switch with a connector that needs to be connected to the Chexit module otherwise the alarm will sound af...
Inadequate power or wrong gauge wire is used the inrush current demand by CX will overload and shutdown the power supply.  You must use the Von Duprin PS873 or newer PS914 supply.   Related soluti...
Using the key from the pull side of the door does not retract the latch bolt on a rim or vertical rod chexit device.
CX98/9975 mortise devices will retract the latch bolt when the key is used on the pull side of the door.
Chexit devices shipped with motor after 8-24-2015. 1. When Chexit device is set for more than zero second rearm time (factory setting is 10 second rearm time) and device goes into alarm immediatel...
Chexit devices shipped with solenoid prior to 8-24-2015. 1.  When Chexit device  is set for more than zero second rearm time (factory setting is 10 second rearm time) and device goes...
The NL key override will not open the door while Chexit rim or vertical rod device is in the arm mode.
On power-up the CO-Series locksets will provide 5 quick RED Schlage Button flashes and 5 quick beeps to indicate that the electronics (credential reader) has been changed.  In order to recover...
When/If the electronics (Credential Reader) changed on a CO-Series lockset, the lock will respond with 3 RED Schlage button flashes and 3 beeps for any key press or credential presentation.&nb...
CO Reader Modules cannot be replaced by Reader Modules with a different credential type; for example, a magnetic swipe credential reader cannot be replaced with a proximity credential rea...
A Credential Reader MAY be replaced with another Credential Reader of the same type; however, a Factory Default Reset must be performed before the lock will function properly.