chexit goes straight into alarm when armed

RELATED FAQS

Question
Answer
Chexit devices shipped with motor after 8-24-2015. 1. When Chexit device is set for more than zero second rearm time (factory setting is 10 second rearm time) and device goes into alarm immediatel...
Chexit devices shipped with solenoid prior to 8-24-2015. 1.  When Chexit device  is set for more than zero second rearm time (factory setting is 10 second rearm time) and device goes...
Chexit devices shipped prior to 8-24-2015 with solenoid driven could cause the Von Duprin CX solenoid to pull and drop and sound the alarm with solid LED or no LED light after the rear...
The following could cause the Chexit device shipped prior to 8-24-2015 with solenoid driven to go into weak alarm with solid LED light: Wrong power supply- Chexit device requires  a...
Followings could cause the Chexit device to go into alarm after the rearm time: Chexit devices shipped after 8-24-2015 with motor driven: Module DPS LED is ON DPS switch contact is open: Close t...
Chexit devices shipped prior to 8-24-2015 with solenoid driven: Chexit device has a RX switch with a connector that needs to be connected to the Chexit module otherwise the alarm will sound af...
Most common issue listed below: Chexit devices shipped after 8-24-2015 with motor driven. The Green wire is not shoeted to the Red wire if no Access Control system is used.If Access Control is us...
 Chexit devices shipped prior to 8-24-2015 with solenoid driven. The GREEN wire is not shorted to the WHITE if no Access Control system is used.If Access Control system is used,...
Using the key from the pull side of the door does not retract the latch bolt on a rim or vertical rod chexit device.
CX98/9975 mortise devices will retract the latch bolt when the key is used on the pull side of the door.