code not working blinking red light

RELATED FAQS

Question
Answer
When the "RED" LED on the 8310-865 RF Receiver is blinking, it is receiving an RF signal (interference) from a non programmed device. When receiving this type of signal, it will not program correct...
Devices were shipped from the factory with motor driven after 8-24-2015. First confirm that you are using PS900 series (902,904,906 or 914) power supply.      1. Mea...
Devices were shipped from the factory with solenoid driven prior to 8-24-2015.  First confirm that you are using a PS873 or PS914 power supply.Measure the DC voltage at the ten wire hardness a...
Inadequate power or wrong gauge wire is used the inrush current demand by CX will overload and shutdown the power supply.  You must use the Von Duprin PS873 or newer PS914 supply.   Related soluti...
Chexit devices shipped prior to 8-24-2015 with solenoid driven could cause the Von Duprin CX solenoid to pull and drop and sound the alarm with solid LED or no LED light after the rear...
This method is only available before the first network communication between an Access Control Panel (ACP) and the lock. Do a Level 1 and Level 2 Factory Default Reset (FDR) to remove any previ...
Manually Setting the RS-485 Address This method is only available before the first network communication between an Access Control Panel (ACP) and the lock. Do a Level 1 and Level 2 Factory De...