Some transformers in the power supplies provide a little humming noise and that is normal. If the humming in Von Duprin PS873 power supply is loud follow these steps. Remove the load from the outp...
  For Product Shipped Prior to August 2012 using the old (black) potted module: a.       0-100 ft 14 gauge wire b.      0-200 ft 12...
 
For Product Shipped Prior to August 2012 using the old (black) potted module:a.       0-100 ft 14 gauge wireb.      0-200 ft 12 gauge wire&nbs...
Since most wire transfer devices such as an EPT or electric hinges cannot provide large gauge wires, we take the small gauge wire into account when determining the overall wire size for the device....
For devices shipped after 8-24-2015 with motor driven:  a.       0-200 ft, use  #18 gauge wire b.      0-500 ft, use #14 gauge wir...
For Product Shipped prior to 8-24-2015 with solenoid driven:          a.       0-100 ft, use #14 Gauge Wire      b.&n...
Chexit devices shipped prior to 8-24-2015 with solenoid driven could cause the Von Duprin CX solenoid to pull and drop and sound the alarm with solid LED or no LED light after the rear...
The PIB300/PIB301 should be located as close as possible to the Access Control Panel.  Do not exceed 500 feet.
Wiring distance from the PIB300/301 to the AD300/301 locksets may be up to 1000 feet (18AWG) for Power and up to 4000 feet (24AWG) for the RS485 data lines.
See the User Guide instructions in the links below
Product Ordered after 7/10/2012 - Product identified by label on QEL motor You no longer need to use the 900-2Q option board (no longer available) with the PS900 power supplies to ...
Product Ordered before 7/10/2012 - Product identified by no label on QEL motor. You must use the 900-2Q option board with the PS900 power supplies to operate the QEL devices.  The attached ta...