electrical requirements for EL

RELATED FAQS

Question
Answer
Applies to L9090EL/EU, L9091EL/EU, L9092EL/EU, L9093EL/EU, L9094EL/EU, L9095EL/EUThe Schlage electrified L-Series wiring diagram can be found here and the re...
Applies to L9080EL/EU. L9082EL/EU (Discontinued)The Schlage electrified L-Series wiring diagram can be found here and the requirements are listed below. 24VAC or 24VDC (maximum 26V, ...
Click here to show the differences of an installed lockcase between the L9090, L9091, L9092, L9093, L9094, L9095 EL/EU and the L9080 EL/EU
For devices shipped after 8-24-2015 with motor driven:  a.       0-200 ft, use  #18 gauge wire b.      0-500 ft, use #14 gauge wir...
For Product Shipped prior to 8-24-2015 with solenoid driven:          a.       0-100 ft, use #14 Gauge Wire      b.&n...
The Von Duprin PS914 power supply must be used on the EL devices with either the 900-2RS or 900-4RL option board since the EL devices requires power supplies set at 24VDC to be able to provide the ...
  You can use a Von Duprin PS914 power supply with any of the following option boards depending on the application. 900-2RS board  will power 1 or 2 devices that do not require timing from pow...
The Von Duprin EL option can be added to any existing 33A/35A, 98/99 series exit devices. 
There is no conversion kit to add EL or ED to an existing 1690 or 1790 series device. All of the components are built into the device, since the device does not have a separate baseplate.&n...
Use a normally closed fire alarm as the input to the power supply option board (PS873-2 or PS914-2RS), this will hold the latch retracted.  During a fire alarm, the contact will open, dropping...
Followings are the list of the electric latch retraction EL/HDEL (hex dogging), QEL (quiet) kits: 114317-00 QELA Mod. Conv. Kit 040061-00 QELA Mod. Conv. Kit...