magnetic hold open

RELATED FAQS

Question
Answer
A 4040SE would not hold the door open if it has : No Voltage or Improper Voltage. Check that the track has proper voltage going to it (24V AC/DC or 120V AC). If 120 volts is supplied...
If an ME Series closer creeps shut or will not hold open, Verify proper voltage is being supplied to the closer, if correct Check the on/off switch. Verify the voltage on the 2 pin co...
To adjust the hold open time on a 4600 (4630/4640) operator: Press the "MODE" button on the control box 1 time to get into programming mode. The "YELLOW" mode indicator LED next to "HOLD OPEN TI...
The correct method (process) for setting the hold open is: The 4110 HEDA arms are handed, verify correct hand arm. (RH or LH stamped on shoe bracket) Loosen the hold open nut at shoe bracket. ...
To install a 4041/4040XP with Rw/PA or Hw/PA arm, you need a minimum of 5-3/8" top rail on the door, measured from the bottom of the stop. If the top rail is less than 5-3/8", you will need to use ...
The 4110 EDA/HEDA can be templated for 100°, 140°, and 180° hold open. The hold open adjustment can be set to hold the door at any position (degree) up to the maximum door opening angle. For "Wi...
If a door is being held open by the LCN SEM 7800/1900 magnet or any ME/SE Series Sentronic LCN closer, you can remotely release that door to close by ordering the following parts and wiring per ST ...
Use a normally closed fire alarm as the input to the power supply option board (PS873-2 or PS914-2RS), this will hold the latch retracted.  During a fire alarm, the contact will open, dropping...