no green light when presenting credentials

RELATED FAQS

Question
Answer
This change was implemented in firmware package CO.A.6 (or later) to help the customer in the communication and coupling process between the CO200 (CO250) and the hand held device (HHD). ...
The green LED is to be lit up until the spindle (Triangles and Key Switch) are aligned properly; providing a visual indication of the problem.  
If the mechanical alignment of the triangles on the back of the outside escutcheon are not aligned, the CO200 or CO250 will not connect with the SUS/HHD and will appear to be unresponsive...
In firmware CO.A.6 (or later) the Schlage button on the CO200 (CO250) will turn green anytime that the spindle triangles on the front escutcheon are out of alignment or the mechanical key switch is...
When unlocking the CO200 door by mechanical key override, the green led will be continuously ON until the key is released. This will occur after firmware CO.A.6 (or later) has been installed int...
A red and green flashing LED's on a QEL indicates the device has been tampered with while power was applied, the push pad was pulled out at least three time. Wait 15 seconds and latchbolt will retr...
The push bar being pulled out three times while power is applied causes the lights to flash and the device to stop retracting.
Check to make sure there is no bind of the latch.
With the new FW package 2.19.0; AD300 FW 2.17.0 and AD400 FW 2.17.0 (released 09/23/2011) the firmware looks for a motor clutch switch change after a motor move command. If there is no motor clutch...
If the triangles in the spring cage spindle are not aligned properly the motor will not move enough to change the clutch switch. Is is very likely with a lock on the bench; but a properly install...
When the new firmware moves the motor three times without seeing the clutch switch change it reports to the SUS diagnostics that the motor is stalled. Aligning the triangles will let the motor move...
If the lock is mounted on the door, it is necessary to adjust the mortis/cylinder tightness and spring cage tailpiece alignments, making sure there is no binding or stopping of the spring...
Just align the triangles per the installation instructions to allow full motor movement.   - This will eliminate the SUS motor STALL report. - This will eliminate the three ...
Yes, the ID3D does have a red/green LED light option.  It's used to indicate successful (green) or rejected (red) hand reads.  The part number is GL-100 and it can only be installed in th...
CO Reader Modules are not individually replaceable, nor can they be swapped between locks. The inside and outside assemblies of a CO lock are a matched/mated set and cannot be swapped to change rea...
Out of the Box, or after a Factory Default Reset, all AD locks can be used in a "Construction Mode".    At launch ...   The AD-Series locks would accept the first card credentia...
Update your device firmware to the latest version to fix this early design / feature update