Senior swing control blowing fuse

RELATED FAQS

Question
Answer
The current (digital control box) activation input wiring harness (# 761464-00) is included in the Sr. Swing parts bag (-518), and has 4 wires in it, Black, White, Yellow, & Gray. This harness p...
The Senior Swing control box is ordered as a 95xx-3462. Example - 9530-3462, 9540-3462.
The Senior Swing Series changed to the "Digital" control box in Sept. of 2006.
For Allegion's recommendation see here.
Following could cause the fuse to blow in Von Duprin PS873 power supply. PS873 power supply provides 2AMP at 24VDC or 4AMP at 12VDC. If this limit is exceeded the fuse will blow in the power sup...
If the Main AC fuse is blowing, the control box is defective and needs to be replaced.  The "Main Fuse" is a (5x20MM) 1 Amp Slow Blow fuse. If the 12VAC fuse is blowing, verify they are not trying...
The main AC fuse would blow if there is a direct short across the AC line. This could be caused by a:1. Defective I/O PC Board (-3180) To check - unplug the control box AC power cable (2 wire) fro...
There is a total of 4 red buttons on the front of the Senior Swing control box. To turn on the display, press and hold any 2 of the 4 red buttons at the same time for approximately 3-5 seconds. Y...
The Senior Swing "control box" is not handed. All Senior Swing motor "gearboxes" are handed, both the 2800 Series concealed and 9500 Series surface mounted operators. The 2800 Series "concealed a...