Top release not always latching

RELATED FAQS

Question
Answer
If mechanism cover plate causes the EL solenoid to drop when slid over the solenoid, the solenoid plunger requires adjustment.  You must lengthen the rod by turning the hex nut in front of the plun...
Check the adjustment and if this does not resolve then you may possibly have a defective center case or bottom latch.
See the link to a video instruction, Concealed Vertical Rod Exit Device Adjustment.Manual steps:Open door and release top latch bolt by inserting a screw driver in the hole at the top of the d...
If your Von Duprin EL (solenoid) device pulls and releases quickly instead of holding the latch retracted, please check all of the items below.In most cases, one or more of these solutions will r...
The following items may cause the exit devices top latch from being held in the retracted position. 1. The top or bottom rods are out of adjustment. 2. The top latch hold back...
Following exit devices 2227/F, 33/3527A/F, 33/3547A/48A/F, 98/9927/F and 98/9947/48/F have similar rod adjustment procedures. All top latches control the bottom latch assemblies. When do...