Von Duprin EL device wiring

RELATED FAQS

Question
Answer
Products shipped on or after August 8, 2012 no longer require the EL wiring adaptor. The ELK Wiring Adaptor (900ELK) was used only when using the PS914 power supply with either the 900-2RS or 900-...
The EL Wiring Adapter is not needed for a CX device.
Use a normally closed fire alarm as the input to the power supply option board (PS873-2 or PS914-2RS), this will hold the latch retracted.  During a fire alarm, the contact will open, dropping...
Reference The 914 Installation instructions.
The 4600 Series operator has both a 12VDC and 24VDC output rated at 1A (combined load) to power strikes, maglocks, and other devices, but an EL device "always" has to have a separate PS914-2RS Seri...
For devices shipped after 8-24-2015 with motor driven:  a.       0-200 ft, use  #18 gauge wire b.      0-500 ft, use #14 gauge wir...
For Product Shipped prior to 8-24-2015 with solenoid driven:          a.       0-100 ft, use #14 Gauge Wire      b.&n...
  For Product Shipped Prior to August 2012 using the old (black) potted module: a.       0-100 ft 14 gauge wire b.      0-200 ft 12...
 
Yes, the QEL device includes a cable assembly part number 110388-00.Since 12/2014, that cable comes in a package (part 116549) with the long cable mentioned above and the small cable that plug...
The EL wiring adapter is not needed for QEL devices.