No, Von Duprin exit alarm ALK and electric latch retraction QEL or EL are installed in the same location and can't be ordered together with the same device.
If mechanism cover plate causes the EL solenoid to drop when slid over the solenoid, the solenoid plunger requires adjustment. You must lengthen the rod by turning the hex nut in front of the plun...
To keep the Von Duprin electric latch retraction EL or QELA exit device dogged (retracted) all day, have your access control, Key pad, key switch, fire alarm contact or any other signals ...
The 4600 Series operator has both a 12VDC and 24VDC output rated at 1A (combined load) to power strikes, maglocks, and other devices, but an EL device "always" has to have a separate PS914-2RS Seri...
Followings are the list of the electric latch retraction EL/HDEL (hex dogging), QEL (quiet) kits:
114317-00
QELA Mod. Conv. Kit
040061-00
QELA Mod. Conv. Kit...
HD-EL (Hex Dogging Electric Latch Retraction) solenoid and plunger can be replaced with standard EL solenoid and plunger on non fire rated exit devices, but this should not be used on a daily basi...
Following could cause the fuse to blow in Von Duprin PS873 power supply.
PS873 power supply provides 2AMP at 24VDC or 4AMP at 12VDC. If this limit is exceeded the fuse will blow in the power sup...
SD is Special cylinder dogging in the center case of 98/99 rim and vertical rod non fire rated devices and is available with standard, EL, QEL, CX and ALK.
Products shipped on or after August 8, 2012 no longer require the EL wiring adaptor.
The ELK Wiring Adaptor (900ELK) was used only when using the PS914 power supply with either the 900-2RS or 900-...
Use a normally closed fire alarm as the input to the power supply option board (PS873-2 or PS914-2RS), this will hold the latch retracted. During a fire alarm, the contact will open, dropping...
Product Ordered after 7/10/2012 - Product identified by label on QEL motor
You no longer need to use the 900-2Q option board (no longer available) with the PS900 power supplies to ...
Product Ordered before 7/10/2012 - Product identified by no label on QEL motor.
You must use the 900-2Q option board with the PS900 power supplies to operate the QEL devices. The attached ta...
The conversion kit does not contain a new mechanism case cover plate. If a cover plate is desired you would need the Fire or Less Dogging Cover Plate for EL conversion kit and panic cover plate fo...
The potted circuit breaker for the Von Duprin EL device does the switching from the 16 amp pull coil on the solenoid to the .33 amp holding coil of the solenoid.
The Von Duprin PS914 power supply must be used on the EL devices with either the 900-2RS or 900-4RL option board since the EL devices requires power supplies set at 24VDC to be able to provide the ...
You can use a Von Duprin PS914 power supply with any of the following option boards depending on the application.
900-2RS board will power 1 or 2 devices that do not require timing from pow...
If your Von Duprin EL (solenoid) device pulls and releases quickly instead of holding the latch retracted, please check all of the items below.In most cases, one or more of these solutions will r...
You can not use these options together on the same device per the following reasons:
QEL/EL device retracts the latch bolt of the exit device allowing entry.
CX (Chexit) device locks the p...
The best way to test the Von Duprin EL solenoid is with an ohm meter. You must test both coils to make sure the solenoid is good. The coil has three wires; green, yellow, and orange. The green...