which power supply for falcon mel exit device

RELATED FAQS

Question
Answer
 One PS902 power supply will run up to six Von Duprin exit alarm ALK devices. PS902  power supply must be set to 24VDC to operate the exit alarm ALK.  Exit alarm ALK exit devices must be as clo...
PS902
Chexit motor driven devices shipped after 8-24-2015:You can use 1 Chexit device with PS902, 3 Chexit devices with PS904, and 4 Chexit devices with PS914 or PS906 power supplies with proper gau...
  For Product Shipped Prior to August 2012 using the old (black) potted module: a.       0-100 ft 14 gauge wire b.      0-200 ft 12...
 
The capabilities of the auto operator and the required operation of the opening will affect the selection of a power supply.
The 900-4RL has two out put for EL devices and signals to the auto operators to open the doors. PS914 power supply is required with 900-4RL option board to operate the EL device and auto operato...
Von Duprin PS914 x 900-4RL supports two EL with two auto operator.
The Von Duprin PS914 power supply must be used on the EL devices with either the 900-2RS or 900-4RL option board since the EL devices requires power supplies set at 24VDC to be able to provide the ...
  You can use a Von Duprin PS914 power supply with any of the following option boards depending on the application. 900-2RS board  will power 1 or 2 devices that do not require timing from pow...
Product Ordered after 7/10/2012 - Product identified by label on QEL motor You no longer need to use the 900-2Q option board (no longer available) with the PS900 power supplies to ...
Product Ordered before 7/10/2012 - Product identified by no label on QEL motor. You must use the 900-2Q option board with the PS900 power supplies to operate the QEL devices.  The attached ta...
The PS9 power supply was discontinued.  The new exit alarm ALK can either use a 9VDC battery or 24VDC regulated power supply. There is no direct replacement for Von Duprin PS9 power supply. Cur...
The Von Duprin PS914 power supply with either the 900-2RS  or the 900-4RL option board is required.