If manually it opens and closes fine, check to make sure one of the actuators is not getting stuck in the on position. Verify that the "Operating Indicator" LED's -- "POWER and SAFETY CLEAR" LED's ...
An error - E04 - is an indication of a constant activation input from either the "Hold Open" switch or a "Wall Activation" switch when the 4600 power is turned on. This condition also occurs when l...
Exterior mounting of the 8310-818 series actuators is not recommended. The 8310-818 series actuators are designed to be jamb mounted on the frame. With that installation, the person will have to ...
To convert a hard wired actuator button to a wireless actuator button you will need the following components:
An RF transmitter.
The 8310-844 transmitter for the (4-1/2" or 6" round, and the ...
To convert an RF actuator button to a hard wired actuator button, simply remove the RF transmitter an connect the hard wiring to the "Common" and "Normally Open" terminals on the the switch.
Yes. Remove the receiver from the operator. Remove the transmitter from the actuator button. Attach 1 wire to the NO (normally open) contact on the actuator switch, and another wire to the COM (com...
An inconsistent opening is normally caused by the arm not being installed correctly. The arm must be installed while the operator gearbox is in the full open position, and the door at 90° open posi...
The installation of the arms with the Benchmark and Falcon Swing Door Operator is similar to the Sr. Swing Series . The arms are installed with the main activation input shorted, the gearbox at the...
To program the 8310-865 receiver:
Set the dip switches 1 to the "OFF" (pulse) position.
Set the dip switches 2 to the "OFF" (0.5s) position.
Momentarily press the " No Delay" or "Delay" ...
Always check the most current revision of the ANSI A156.19 standard for recommendation or requirement of the location of a Knowing Act switch.
2019 ANSI A156.19 states the requirement of the ...
If a 4600 clicks, but won't open the door:
Verify proper connection of all the control box connectors.
Verify correct manual operation of door.
Verify actuator connections and any strike/maglo...
If the 9100 Series Benchmark operator does not open when the actuator is pushed:
Verify the unit has 120 volts applied to it.
Verify the the power light on the control box is on. If not, check ...
The 6111 electric strike can be used only on non rated openings less bottom rod with pullman top latch (use ES prefix when ordering device). Device back set will change to match the centerline of t...
Use the PS902-2RS power supply with LCN auto operator on single door, PS904-2RS power supply on double door and PS904/906-2RS-2RS for 2 pair of QELA is required for basic operation with a...