Maximum glass light sizes for 3 hour fire doors is as follows: Wire glass - not approved for use in 3 hour fire doors. Ceramic glass: UL & ITS/WH allow one (1) light with 100 square inc...
Non fire rated doors can be furnished with a maximum 3" diameter hole for viewer preparations. Fire rated doors have a 3/4" maximum holes size unless otherwise listed by UL or ITS/WHI. Viewers mus...
Astragals are required on: 3 hour fire rated pairs: Double doors - swinging in the same direction Double Egress - swinging in opposite directions Fire rated Dutch Doors Fire rated 1 3/4" t...
Maximum glass light size for a 90 minute (1 1/2 hour) door depends on the type of glass being installed. Wire glass = 100 square inches is max exposed glass when wire glass is used. Note - ma...
A UL 20 minute fire rating is the maximum fire rating for a Full Glass (FG) door design. A14-Series door construction: Max fire rating is 20 minute. UL label only FG must use Over-Lapping Stee...
Yes, Steelcraft doors and/or frames are available and can carry a UL, WH or FM label. The type of fire label (UL, WH or FM) is dictated by the specifications and local building code. Doors ...
A fire rated door for 3 hours can have one glass light maximum: 100 square inches and must have an approved glass (Firelite type) Max glass size cannot exceed 12" in width or 33" in height. Wi...
GrainTech® is a Steelcraft door option which provides a wood grained pattern which is embossed into both face sheets of the door. GrainTech doors are factory stained and top coated with a cle...
Yes, as an option, Steelcraft doors are available with factory prepared for the 98/9949 Concealed Vertical Cable Exit Device. L, B, CE, T and CE-Series doors are available factory prepared Door...
Dutch doors are available as Fire Rated door assemblies and have similar component requirements as a single leaf fire door. Exceptions are as follows: The Dutch Door assembly must have a lock...
Maximum UL Fire Rated door sizes are as follows: A-Series: 4' 0" X 8' 0" single door 8' 0" X 8' 0” double door or pairs B-Series 4' 0" X 10' 0" single door 8' 0" X 10' 0” double doo...
The SED/MED series closers where discontinued in 2000. The SE or ME series from LCN can be used as replacements to provide a hold open feature, but will not have the smoke detector...
The 6223-FSE electric strike is fire rated for pairs of wood doors, but check with wood door manufacturer to see if they have been approved for this application.
The 909 strike is used in single and paired non-fire rated and single fire rated openings.  The 954 strike is used in fire rated paired openings.
The 1609 strike cannot be used with Von Duprin XP98/99 exit device.