The 3130 Series closer is UL listed- Fire Rated (UL-10C) for up to 3 Hr.
The Door and Frame Manufacturer needs to be contacted to verify their Door/Frame rating would not be ...
The old 4030/4130 closers and arms are obsolete, there is nothing to replace them. No arm from other closers will fit
There is no closer that can replace the old 4030 series closer with the exa...
STANDARD ROD AND SHOE: 4020, 4031, 1460, 1520, 1370, 1070, 1260, 4640, 4820 is: 8 3/8”
LONG ROD AND SHOE: 4020: 4031, 1460, 1520, 1370, 1070, 1260, 4640, 4820 is: 12 3/8”
STANDARD ROD AN...
How to: What are the steps to adjust a door closer?Facts: All LCN and FALCON door closers will have 3 regulating valves and a spring adjustment. All closers with a "Delay" feature ...
There are a few things that can cause a closer to slam.
The closer could be adjusted incorrectly. Turn all regulating screws clockwise until they stop. Then open each valve 1 and 1/2 turns. If t...