Yes, fire rated exit devices can have electric latch retraction. However, the devices must be tied into a fire alarm system to remove power from the units so the doors will be latched in the ...
The 6111 electric strike can be used only on non rated openings less bottom rod with pullman top latch (use ES prefix when ordering device). Device back set will change to match the centerline of t...
A fire rated door for 3 hours can have one glass light maximum:
100 square inches and must have an approved glass (Firelite type)
Max glass size cannot exceed 12" in width or 33" in height.
Wi...
Yes, as an option, Steelcraft doors are available with factory prepared for the 98/9949 Concealed Vertical Cable Exit Device.
L, B, CE, T and CE-Series doors are available factory prepared
Door...