CAN LEVER SHUNT CHEXIT ALARM

RELATED FAQS

Question
Answer
You can use the E996L electric trim with Chexit 98/99 series exit device.
Chexit devices shipped prior to 8-24-2015 with solenoid - the solenoid pulls and drops, the alarm sounds, there is a solid LED or no LED light after the rearm t...
The following could cause the Von Duprin CX solenoid ( devices shipped prior to 8-24-2015) to pull and drop and sound the alarm with solid LED light. Wrong power supply, requires Von Duprin ...
The following could cause the Chexit solenoid ( devices shipped prior to 8-24-2015) pulls in then drop out with no alarm. Mechanical adjustment such as vertical rods. Disconnect t...
For Chexit devices shipped after 8-24-2015 with motor driven connect your normally closed contact from access control system between green and red on the twelve field wire ...
For Motor driven Chexit devices shipped from the factory after 8-24-2015, the Chexit Secure Relay Contacts( white and violet wires) change state to signal the device is not secure. Check the f...
For Solenoid driven Chexit devices shipped from the factory prior to 8-24-2015, the following could cause the device not to provide delay egress:Measure the voltage between green and orange wires o...
Followings could cause the Chexit device to go into alarm after the rearm time: Chexit devices shipped after 8-24-2015 with motor driven: Module DPS LED is ON DPS switch contact is open: Close t...
Chexit devices shipped prior to 8-24-2015 with solenoid driven: Chexit device has a RX switch with a connector that needs to be connected to the Chexit module otherwise the alarm will sound af...
To get a dry contact signal from a Chexit device to monitor the alarm, use the blue and brown wires (do not connect the blue to the red)  of the harness connector cable tha...
Fire alarm contact would tie right into the Von Duprin Chexit device not to the PS914 power supply. There is no requirement to install the fire alarm board.
The Chexit device has a different base plate and center case than the ALK.  The Chexit device would need to be replaced with an ALK device.
The following could cause the Chexit device shipped prior to 8-24-2015 with solenoid driven to go into weak alarm with solid LED light: Wrong power supply- Chexit device requires  a...
If the Chexit device shipped prior to 8-24-2015  is not adjusted correctly ( Check vertical rod or Mortise finger) without using the door position switch and nuisance delay is&n...
 
Chexit devices shipped with motor after 8-24-2015. 1. When Chexit device is set for more than zero second rearm time (factory setting is 10 second rearm time) and device goes into alarm immediatel...
Chexit devices shipped with solenoid prior to 8-24-2015. 1.  When Chexit device  is set for more than zero second rearm time (factory setting is 10 second rearm time) and device goes...
The Von Duprin Chexit device will not automatically rearm itself after a fire alarm clears.  After a Fire Alarm has triggered the Von Duprin Chexit device, the device must be manually reset&nb...