can you use XP devices with electric strikes

RELATED FAQS

Question
Answer
This is not a recommended application as the electric strike does not have the same holding force as the XP98/99 rim exit device. Typically the XP device will withstand a higher force than electr...
Von Duprin does not recommend using XP98/99 devices with any electric strike.   Von Duprin recommends using the standard 98/99 rim device.   
The Von Duprin XP98/99 device uses a different strike than standard 98/99 device. The 909 strike is for non fire rated XP devices and the 954 strike is for the fire rated XP device. 49/9954 mul...
The 909 strike is used in single and paired non-fire rated and single fire rated openings.  The 954 strike is used in fire rated paired openings.
The 1609 strike cannot be used with Von Duprin XP98/99 exit device.
This application is not recommended as elelctric strikes have never been tested with XP98/99 exit device because it would defeat the XP device holding force purpose.  
The 22, 33/35A and 98/99 rim exit devices: The 6111 is the most common electric strike to be used with these devices 6112 and 6113 electric strikes also could be used The 6300 surface mount el...
The 6111 electric strike can be used only on non rated openings less bottom rod with pullman top latch (use ES prefix when ordering device). Device back set will change to match the centerline of t...
Not for use in fire rated openings.
The 5547 device can be ordered with an ES prefix to work in conjunction with an electric strike. This requires LBR and can only be done on non-fire rated applications. To convert an existing ...