The following could cause the Von Duprin CX solenoid ( devices shipped prior to 8-24-2015) to pull and drop and sound the alarm with solid LED light.
Wrong power supply, requires Von Duprin ...
The following could cause the Chexit solenoid ( devices shipped prior to 8-24-2015) pulls in then drop out with no alarm.
Mechanical adjustment such as vertical rods. Disconnect t...
The following could
cause the Chexit device shipped prior to 8-24-2015 with solenoid driven to
go into weak alarm with solid LED light:
Wrong power supply- Chexit
device requires a...
Inadequate power or wrong gauge wire is used the inrush current demand by CX will overload and shutdown the power supply. You must use the Von Duprin PS873 or newer PS914 supply.
Related soluti...
Chexit devices shipped prior to 8-24-2015 with solenoid driven could cause the Von Duprin CX solenoid to pull and drop and sound the alarm with solid LED or no LED light after the rear...
Chexit devices shipped with motor after 8-24-2015.
1. When Chexit device is set for more than zero second rearm time (factory setting is 10 second rearm time) and device goes into alarm immediatel...
Chexit devices shipped with solenoid prior to 8-24-2015. 1. When Chexit device is set for more than zero second rearm time (factory setting is 10 second rearm time) and device goes...
Most common issue listed below:
Chexit devices shipped after 8-24-2015 with motor driven.
The Green wire is not shoeted to the Red wire if no Access Control system is used.If Access Control is us...
Chexit devices shipped prior to 8-24-2015 with solenoid driven. The GREEN wire is not shorted to the WHITE if no Access Control system is used.If Access Control system is used,...