chexit device card reader

RELATED FAQS

Question
Answer
When CX99L-BE is not armed with key cylinder on the device or shunted by card reader, the exterior 996LBE lever trim will release.
The access control system should provide Common and Normally Closed dry contact that will connect between the green and white wire on the CX 10 wire harness.
The standard Von Duprin mechanical or electrical 98/99/33/35 exit devices can not be converted to a CX98/99 or CX33/35 device. Von Duprin CX98/99 or CX33/35 has a different base p...
For Chexit devices shipped after 8-24-2015 with motor driven connect your normally closed contact from access control system between green and red on the twelve field wire ...
Chexit devices shipped prior to 8-24-2015 with solenoid driven: A normally closed card reader contact, key pad contact or any other control contact connects to the Green an...
The 4600 Series operator has both a 12VDC and 24VDC output rated at 1A (combined load) to power strikes, maglocks, and other devices, but an EL device "always" has to have a separate PS914-2RS Seri...
For F-series HandPunch devices:    The top-mount PROX reader is available only for the HP-3000 reader.  The PROX reader on a HandPunch 3000 is able to read standard 26-bit ...
Customers will need to use the Schlage Utility Software (SUS) on the HHD lock programming device to set the desired magnetic track to be read for access control, if not using default Track 2&n...
If an access control system is not available to test the card output on a hand reader, this card emulation test can be done to verify the card format is correct.  These steps will guide you in...