chexit external inhibit unlock

RELATED FAQS

Question
Answer
For Chexit devices shipped after 8-24-2015 with motor driven connect your normally closed contact from access control system between green and red on the twelve field wire ...
Chexit devices shipped prior to 8-24-2015 were solenoid driven: A normally closed card reader contact, key pad contact or any other control contact connects to the G...
For Rim / Vertical Devices: No,  RX 996 trim can not be used to inhibit Chexit.  The trim lever can not be rotated while the Chexit is armed, and therefore the RX996 switch will not...
Current exit alarm ALK released in November 2010 does ship standard with an EI (external inhibit) option.  ALK shipped prior to this would only have EI if ordered as a Special option.
The current Von Duprin ALK comes standard with the External Inhibit feature.
If Chexit device LED blink once when you turn the unit on, the External inhibit green wire is not by passed or not connected to the access control normally closed contact.  For devices sh...