Chexit devices shipped with motor after 8-24-2015.
1. When Chexit device is set for more than zero second rearm time (factory setting is 10 second rearm time) and device goes into alarm immediatel...
Chexit devices shipped with solenoid prior to 8-24-2015. 1. When Chexit device is set for more than zero second rearm time (factory setting is 10 second rearm time) and device goes...
Chexit devices shipped prior to 8-24-2015 with solenoid driven could cause the Von Duprin CX solenoid to pull and drop and sound the alarm with solid LED or no LED light after the rear...
The following could cause the fuse to blow in the power supply with devices shipped prior to 8-24-2015 with solenoid driven when Chexit device is arming.
Wrong power supply Confirm PS873 or...
Most common issue listed below:
Chexit devices shipped after 8-24-2015 with motor driven.
The Green wire is not shoeted to the Red wire if no Access Control system is used.If Access Control is us...
Chexit devices shipped prior to 8-24-2015 with solenoid driven. The GREEN wire is not shorted to the WHITE if no Access Control system is used.If Access Control system is used,...
Followings could cause the Chexit device to go into alarm after the rearm time:
Chexit devices shipped after 8-24-2015 with motor driven:
Module DPS LED is ON
DPS switch contact is open: Close t...
Chexit devices shipped prior to 8-24-2015 with solenoid driven: Chexit device has a RX switch with a connector that needs to be connected to the Chexit module otherwise the alarm will sound af...