chexit latch re-arm

RELATED FAQS

Question
Answer
If a door position switch (DPS) is connected across the green and white wires of the CX the CX would go into alarm if the door is held open when it attempts to rearm.  If no DPS is used the ...
Followings could cause the Chexit device to go into alarm after the rearm time: Chexit devices shipped after 8-24-2015 with motor driven: Module DPS LED is ON DPS switch contact is open: Close t...
Chexit devices shipped prior to 8-24-2015 with solenoid driven: Chexit device has a RX switch with a connector that needs to be connected to the Chexit module otherwise the alarm will sound af...
You can not use these options together on the same device per the following reasons: QEL/EL device retracts the latch bolt of the exit device allowing entry. CX (Chexit) device ...
The following could cause the Von Duprin CX solenoid ( devices shipped prior to 8-24-2015) to pull and drop and sound the alarm with solid LED light. Wrong power supply, requires Von Duprin ...
The following could cause the Chexit solenoid ( devices shipped prior to 8-24-2015) pulls in then drop out with no alarm. Mechanical adjustment such as vertical rods. Disconnect t...
Inadequate power or wrong gauge wire is used.  The inrush current demand by CX will overload and shutdown the power supply if undersized.  You must use the Von Duprin PS873 or...
No, LCN does not have an electronic hold open closer (SE/ME Series) that will provide a solid 180° hold open position. The 3130SE has an adjustable hold open position from 85° to 110° maximum. ...