chexit solenoid disconnected

RELATED FAQS

Question
Answer
Only applicable for solenoid driven Chexit devices shipped from the factory prior to 8-24-2015; Chexit solenoid coil resistance between the green and orange wires is 110-140 ohm and betw...
Make sure the proper power supply (PS873 or PS914) and proper gauge and run wire is used for Chexit devices shipped prior to 8-24-2015 with solenoid driven. Related Solution: What wire&n...
The part number for "CX Wiring Assembly" also called "Ten Wire Connector" is 112018-00.  
The following could cause the Von Duprin CX solenoid ( devices shipped prior to 8-24-2015) to pull and drop and sound the alarm with solid LED light. Wrong power supply, requires Von Duprin ...
The following could cause the Chexit solenoid ( devices shipped prior to 8-24-2015) pulls in then drop out with no alarm. Mechanical adjustment such as vertical rods. Disconnect t...
Chexit devices shipped prior to 8-24-2015 with solenoid - the solenoid pulls and drops, the alarm sounds, there is a solid LED or no LED light after the rearm t...