Delayed egress hardware prevents a door from being opened from the egress side, usually for a period of 15 seconds. This type of device is often used to prevent theft, while maintaining life safe...
There is not a fully self-contained delayed egress like a Von Duprin Chex-It device but the Falcon RX-25 Series can perform a delayed egress by using the DE5300 controller, power supply, ...
The Von Duprin Chexit-BOCA has special software. Following is the function of this software:
When Chexit device push bar is pushed and goes into alarm it will release in 15/30 sec...
The Von Duprin Chexit device will not automatically rearm itself after a fire alarm clears. After a Fire Alarm has triggered the Von Duprin Chexit device, the device must be manually reset&nb...
You can not use these options together on the same device per the following reasons:
QEL/EL device retracts the latch bolt of the exit device allowing entry.
CX (Chexit) device ...
For Motor driven Chexit devices shipped from the factory after 8-24-2015, the Chexit Secure Relay Contacts( white and violet wires) change state to signal the device is not secure. Check the f...
For Solenoid driven Chexit devices shipped from the factory prior to 8-24-2015, the following could cause the device not to provide delay egress:Measure the voltage between green and orange wires o...
The release delay time for the Chexit is programmed into the Chexit module and cannot be changed in the field.
The ability to change the delay time is restricted by the UL listing of the devi...