Yes, hospital stops are available on fire rated frames.
Maximum approval = 3 hour
Maximum sizes:
singles up to 4'0" x 8'0"
pairs up to 8'0" x 8'0"
Maximum hospital stop height 6" from bot...
Hospital Stops are located at the bottom of the frame jambs and/or mullions. The integral door stops are terminates above floor line and is closed with a 45° or 90° angle to facilitate cleaning at ...
Fire Rated three (3) frames are available in the following maximum door opening sizes:
F and FN-Series frame:
4' 0" X 10' 0" single door opening
8' 0" X 10' 0” double door opening
MU-Ser...
Yes, wood doors can be used and installed in most hollow metal frame applications including FE-Series and DE-Series Double Egress frames.
Caution - For fire rated applications the wood door manufa...
A Double Egress frame is a double door frame prepared to receive two single-acting doors swinging in opposite directions (both doors are) the same hand. These openings are installed in cross corrid...
No. Fire rated double egress frames must be a stand alone 3 sided frame assembly.
If transom lights and/or sidelights are required, they must be built and installed as separate Fire Window assemb...
Hospital Stops are available as either:
45° Hospital Stop - the stop of the frame terminates at a 45° angle
90° Hospital Stop - the stop of the frame terminates at a 90° angle
The type of hos...
Purpose:
When there is concern for the weight of overhead wall construction, or, when multiple surface applied hardware components are being used. This continuous channel has the ability to spre...