EL DEVICE NOT STAYING PULLED IN

RELATED FAQS

Question
Answer
If your Von Duprin EL (solenoid) device pulls and releases quickly instead of holding the latch retracted, please check all of the items below.In most cases, one or more of these solutions will r...
Use a normally closed fire alarm as the input to the power supply option board (PS873-2 or PS914-2RS), this will hold the latch retracted.  During a fire alarm, the contact will open, dropping...
Following could cause the EL device to pull and drop repeatedly.  Short to ground  on EL wiring.  Incorrect wire gauge used.  For wire run and gauge requirements, click HERE  Wrong power suppl...
The following items may cause the exit devices top latch from being held in the retracted position. 1. The top or bottom rods are out of adjustment. 2. The top latch hold back...
Following exit devices 2227/F, 33/3527A/F, 33/3547A/48A/F, 98/9927/F and 98/9947/48/F have similar rod adjustment procedures. All top latches control the bottom latch assemblies. When do...