electric strike change voltage

RELATED FAQS

Question
Answer
The Von Duprin 6000 series electric strike can be converted by ordering the appropriate kits below.  Kits include the solenoid, plunger, spring, and washer. 6000 Series solenoid Kit 1...
The 5100 strike details are listed below: Only operates with 12VDC or 24VDC power supply. Will not operate with AC transformer. 12 or 24VAC can be converted to 12/24VDC using Von Duprin SO12 o...
For all models of 6000 series electric strike, except the 6300 & 6400, the color of the solenoid wires determine the voltage.  Black wires are used on 24VDC solenoids and yellow wir...
The strike will always be DC.  By using a SO24 or SO12(rectifiers) you will be able to convert the AC waveform from a transformer to a DC waveform that will be acceptable by the 6000 series strikes.
The 5547 device can be ordered with an ES prefix to work in conjunction with an electric strike. This requires LBR and can only be done on non-fire rated applications. To convert an existing ...
The 4630/4630 operator has a 12 VDC and 24 VDC output that can power an electric strike or maglock. The wiring diagrams are shown on page 14 of the installation instructions (attached). 4600 Insta...
Follow the steps below to troubleshoot the problem. Measure the voltage at the electric strike. If the strike is FSE and not locking there should be no voltage at the strike and if it is FS there ...