ITS/WHI Fire Rated three (3) frames are available in the following maximum door opening sizes:
F and FN-Series:
4' 0" X 10' 0" single door
8' 0" X 10' 0” double door or pairs
MU-Series:
...
Fire Rated three (3) frames are available in the following maximum door opening sizes:
F and FN-Series frame:
4' 0" X 10' 0" single door opening
8' 0" X 10' 0” double door opening
MU-Ser...
DW-Series Fire Rated Borrowed Lights are available in the following sizes:
60 minute (1 hour) rating = 2721 square inches of visible glass.
maximum frame rabbet to rabbet dimensions = 78 1/4...
On fire rated transom and/or sidelight frames and fire rated window frames, Steelcraft labeling procedures only control the O/A width and/or height of the frames based on wall condition. The amount...
F-Series frames are available without returns:
Fire Rated frames must have welded corners.
Frames must include weled in wood or steel stud anchors.
Installation requirements:
...
ASTM E-119 is a test standard for walls, partitions and floor or roof systems:
This test standard is also used for ceramic type glasses when used as window wall and/or borrowed light frames.
...
Yes, wood doors can be used and installed in most hollow metal frame applications including FE-Series and DE-Series Double Egress frames.
Caution - For fire rated applications the wood door manufa...
Yes, hospital stops are available on fire rated frames.
Maximum approval = 3 hour
Maximum sizes:
singles up to 4'0" x 8'0"
pairs up to 8'0" x 8'0"
Maximum hospital stop height 6" from bot...
Transom panels are available in the following constructions:
1 3/4" thick panels with interior construction similar to an L-Series door installed into a frame either
Without a transom bar - r...