The correct method (process) for setting the hold open is:
The 4110 HEDA arms are handed, verify correct hand arm. (RH or LH stamped on shoe bracket)
Loosen the hold open nut at shoe bracket.
...
If an ME Series closer creeps shut or will not hold open,
Verify proper voltage is being supplied to the closer, if correct
Check the on/off switch. Verify the voltage on the 2 pin co...
If a door is being held open by the LCN SEM 7800/1900 magnet or any ME/SE Series Sentronic LCN closer, you can remotely release that door to close by ordering the following parts and wi...
A 4040SE would not hold the door open if it has :
No Voltage or Improper Voltage. Check that the track has proper voltage going to it (24V AC/DC or 120V AC).
If 120 volts is supplied...
To install a 4041/4040XP with Rw/PA or Hw/PA arm, you need a minimum of 5-3/8" top rail on the door, measured from the bottom of the stop. If the top rail is less than 5-3/8", you will need to use ...