is VD El Device solenoid driven

RELATED FAQS

Question
Answer
If mechanism cover plate causes the EL solenoid to drop when slid over the solenoid, the solenoid plunger requires adjustment.  You must lengthen the rod by turning the hex nut in front of the plun...
To keep the Von Duprin electric latch retraction EL or QELA exit device dogged (retracted) all day, have your access control, Key pad, key switch, fire alarm contact or any other signals ...
The threaded bushing on the solenoid plunger requires 8-9 threads showing to operate correctly.
It can but the solenoid will need to be purchased through New England Door Closer as the factory discontinued the old ELR solenoid (part #650092-000) in June 2010.
The EL94/95 Inpact solenoid is different than the EL33A/35A/98/99 solenoid. The part for the Inpact solenoid is 113189.  
As of 1/16/2013, the 113189-00 EL INPACT SOLENOID/PLUNGER ASSY is no longer available.
The Falcon EL devices can be operated in a continuous duty cycle.
Products shipped on or after August 8, 2012 no longer require the EL wiring adaptor. The ELK Wiring Adaptor (900ELK) was used only when using the PS914 power supply with either the 900-2RS or 900-...