The Falcon 25R rim device can be used with 6111 electric strike on single or double doors.
Additional Information:
The Von Duprin 4854/9854 mullion is required when using 25R...
For the backset see the Falcon (F)25-R template; T-1201 for Metal Door, W-1201 for Wood Door.
For Single Doors, the distance from the surface of the raised stop to the Centerline of the device is...
The Von Duprin XP98/99 device uses a different strike than standard 98/99 device.
The 909 strike is for non fire rated XP devices and the 954 strike is for the fire rated XP device.
49/9954 mul...
The centerline of 6223 is the same as the centerline of the mortise latch bolt.
So the centerline of the mortise latch bolt or center line of the 6223 is 15/32" above the centerline of the device.
None of the Von Duprin electric strikes will work in a retrofit application where the normal standard mechanical strike is mounted to the frame because none of them are thin enough to fit in...
The 6111 electric strike can be used only on non rated openings less bottom rod with pullman top latch (use ES prefix when ordering device). Device back set will change to match the centerline of t...
Minimum dimensions to cutouts for glass lights:
Vertical edge of door to edge of cutout = 5 29/32"
Top of door to top of cutout = 6"
Bottom of door to bottom of cutout = 10"
Reinforcing chann...
The top rod is required for proper operation. The top latch controls both the top & bottom rods and without the top latch/rod the bottom latch would release when pushpad or trim was used but then ...
The minimum top and bottom butt hinge locations are as follows:
To the hinge centerline:
4 1/2" and 5" hinges = 5 3/8" is the minimum location from top of door to centerline of the first hi...
The 1461 Rw/PA requires a 4-3/8" minimum top rail on the door without the use of a drop plate.
If top rail is less than 4-3/8" a 1460-18PA drop plate will have to be used.
The minimum top rail required to mount a 4110 closer is 5-1/8" measured from the stop of the frame.
If the top rail is less than 5-1/8" the 4110-18 drop plate is required.
There are 2 types of door coordinators available:
Bar Coordinators (Ives COR Series):
Surface mounted to the bottom surface of the frame soffit.
The active door lever, located nearest to th...
The 576A or 576B strikes can be used on wood doors but you should check with door manufacturer if it is a fire-rated door to make sure there are no conflicts.
For Steelcraft frame anchor locations refer to the frame "Anchoring Systems" section of Steelcraft's Tech Data Manual pages 2.4.1 thru 201.16.Basic guidelines are as follows:Anchor Quantities:• 3 p...
HH hurricane rated devices usually have a deferent strike and fire rated mullion.
Standard 98/99 series exit devices can be converted to HH by changing the strike and mullion on pair of doors.
...
To use the 5547 with an electric strike you would need the ES top rod & latch part number 050656-00 and remove the bottom rod and latch. The 6213 electric strike is recommended with 5547LBR, non fi...
See the link to a video instruction, Concealed Vertical Rod Exit Device Adjustment.Manual steps:Open door and release top latch bolt by inserting a screw driver in the hole at the top of the d...
The Benchmark III control has a 24VDC, 2.5 amp power supply, and built in relay for controlling electric strikes or other accessories less than 2.5 amps current load.
For a fail secure strike, r...