NoTour credentials are not full but getting error code saying they are

RELATED FAQS

Question
Answer
The NoTour function only allows writing to 11 sectors on the fob.  Each lock added to a user uses 1 sector.  Once those 11 sectors are full, No Tour is not available.  You can ...
This error indicates the credential was previously designated as a master credential on that site and was deleted. Deleted master credentials cannot be used again on the same site.  Recommend ...
When trying to program a CM lock, it may display an error code with a solid green light and 10 read flashes. This indicates the lock has already been programmed with computer software and manual pr...
Early versions (12/09 ) of the AD200 User Guide in many DEMO kits incorrectly state the Programming sequence to change the a programming code. It shows entering the new programming code o...
Error Code 407 usually indicates that NoTour sectors are full. It could also mean a FW update to the MT20w is needed. Try updating FW and confirming that at least 1 sector is available in...
With the new FW package 2.19.0; AD300 FW 2.17.0 and AD400 FW 2.17.0 (released 09/23/2011) the firmware looks for a motor clutch switch change after a motor move command. If there is no motor clutch...
If the triangles in the spring cage spindle are not aligned properly the motor will not move enough to change the clutch switch. Is is very likely with a lock on the bench; but a properly install...
When the new firmware moves the motor three times without seeing the clutch switch change it reports to the SUS diagnostics that the motor is stalled. Aligning the triangles will let the motor move...
If the lock is mounted on the door, it is necessary to adjust the mortis/cylinder tightness and spring cage tailpiece alignments, making sure there is no binding or stopping of the spring...
Just align the triangles per the installation instructions to allow full motor movement.   - This will eliminate the SUS motor STALL report. - This will eliminate the three ...