Question
Answer
FBC Approvals: Yes, Steelcraft doors do meet the Florida Building Code (FBC) Protocols (TAS 201, TAS 202 & TAS 203) Missile impact & ASTM E-330 applications Dade County NOAs: Yes,...
Steelcraft Paladin PW-Series doors and FP-Series frames meet FEMA Tornado Resistant requirements and have been designed and tested to meet the requirements of FEMA 361 guidelines and ANSI ICC500....
Grouting frames is: A process done in the field during hollow metal frame installation  The internal cavity of the frame is fill with masonry or mortar It is intended to mainly provide ...
Yes. 1 7/16" thick glass but a special rabbet size is required. The size of rabbet required for the frames would depend on the size of the glazing bead being used. For 1" wide glazing stops, ...
No. The Steelcraft H-Series hurricane door does not meet the FEMA 361 guidelines. The Paladin (PW14-Series) door does meet the FEMA 361 guidelines.
Tornado shelter applications require the use of Paladin PW14-Series doors and FP14-Series frames: Tornado shelter doors are a tested system comprising of the door, frame and hardware. ...
The backset is 2 3/4" from edge of door to the center line of the device and strike. The preparation for the WS98/99 strike must be specified when placing order for the frame.
The following hinges are available on Paladin series doors and frames: Butt hinges -  4 1/2", 5" or 6" ball bearing type either standard or heavy duty Continuous hinges - full mortise...
Astragals are required on: 3 hour fire rated pairs: Double doors - swinging in the same direction Double Egress - swinging in opposite directions Fire rated Dutch Doors Fire rated 1 3/4" t...
LCN "does not" recommend the use of SRT screws is wood doors. LCN "only" recommends the use of Wood Screws in wood doors and frames, as noted on the installation instructions.