Power Supply Two Magnetic Locks

RELATED FAQS

Question
Answer
Applies to L9090EL/EU, L9091EL/EU, L9092EL/EU, L9093EL/EU, L9094EL/EU, L9095EL/EUThese models require 12/24 VDC with a peak current of 0.4 amps.  The following po...
Applies to L9080EL/EU, L9082EL/EU (Discontinued)The Schlage L9080 EU/EL and L9082 EU/EL require 24 VAC/VDC with a peak current of 1.3 Amps at 5 to 10 second intervals and a holding curren...
The PS861 will not power an EL device.  The high 16Amp current of the EL requires the PS914-2RS, PS914-4RL or the older PS873-2 power supply to operate.
The 4600 Series operator has both a 12VDC and 24VDC output rated at 1A (combined load) to power strikes, maglocks, and other devices, but an EL device "always" has to have a separate PS914-2RS Seri...