Question
Answer
For Motor driven Chexit devices shipped from the factory after 8-24-2015, the Chexit Secure Relay Contacts( white and violet wires) change state to signal the device is not secure. Check the f...
For Solenoid driven Chexit devices shipped from the factory prior to 8-24-2015, the following could cause the device not to provide delay egress:Measure the voltage between green and orange wires o...
Chexit devices shipped after 8-24-2015 with motor driven:Use the Alarm Relay Contacts on Field Wiring Cable, blue and brown wires of the Chexit device.Connect the blue wire to +24VDC (red wire on F...
Chexit devices shipped prior to 8-24-2015 with solenoid driven:Use the external alarm contact, blue and brown wire on Chexit device.Connect the blue wire to the red wire and connect the brown wire ...
To get a dry contact signal from a Chexit device to monitor the alarm, use the blue and brown wires (do not connect the blue to the red)  of the harness connector cable tha...
The E996L-FSE trim is needed if the application requires fail-secure operation from the trim side of the opening. When power is out on Chexit device, E996L-FSE trim will remain locked to ...
For Chexit devices shipped after 8-24-2015 with motor driven connect your normally closed contact from access control system between green and red on the twelve field wire ...