solenoid will not fully unlatch

RELATED FAQS

Question
Answer
If mechanism cover plate causes the EL solenoid to drop when slid over the solenoid, the solenoid plunger requires adjustment.  You must lengthen the rod by turning the hex nut in front of the plun...
A 4040SE would not hold the door open if it has : No Voltage or Improper Voltage. Check that the track has proper voltage going to it (24V AC/DC or 120V AC). If 120 volts is supplied...
If your Von Duprin EL (solenoid) device pulls and releases quickly instead of holding the latch retracted, please check all of the items below.In most cases, one or more of these solutions will r...
The following could cause the Von Duprin CX solenoid ( devices shipped prior to 8-24-2015) to pull and drop and sound the alarm with solid LED light. Wrong power supply, requires Von Duprin ...
The following could cause the Chexit solenoid ( devices shipped prior to 8-24-2015) pulls in then drop out with no alarm. Mechanical adjustment such as vertical rods. Disconnect t...
To keep the Von Duprin electric latch retraction EL or QELA exit device dogged (retracted) all day, have your access control, Key pad, key switch, fire alarm contact or any other signals ...
The resistance readings for a Falcon 24 or 25 Series EL solenoid should read;Green to Yellow = Pull Coil, should measure between 1 and 2 ohms of resistance. Green to Orange = Hold Coil, s...
  For Product Shipped Prior to August 2012 using the old (black) potted module: a.       0-100 ft 14 gauge wire b.      0-200 ft 12...
 
If an ME Series closer creeps shut or will not hold open, Verify proper voltage is being supplied to the closer, if correct Check the on/off switch. Verify the voltage on the 2 pin co...