what wire gauge is required for L electrified mortise locks

RELATED FAQS

Question
Answer
Supply wires - 24AWGRX wires - 20AWGLX wires - 20 AWG
  For Product Shipped Prior to August 2012 using the old (black) potted module: a.       0-100 ft 14 gauge wire b.      0-200 ft 12...
 
For devices shipped after 8-24-2015 with motor driven:  a.       0-200 ft, use  #18 gauge wire b.      0-500 ft, use #14 gauge wir...
For Product Shipped prior to 8-24-2015 with solenoid driven:          a.       0-100 ft, use #14 Gauge Wire      b.&n...
The PIB300/PIB301 should be located as close as possible to the Access Control Panel.  Do not exceed 500 feet.
Wiring distance from the PIB300/301 to the AD300/301 locksets may be up to 1000 feet (18AWG) for Power and up to 4000 feet (24AWG) for the RS485 data lines.
See the User Guide instructions in the links below
RX wiring on all L9000 locks with RX switch manufactured after January 2, 2017:The L-Series switched to a handed modular three-wire request to exit (RX) switch. This change was originally completed...
Specific to the RX switch installed into the L9080EL/EU and L9082EL/EU and L9000 mechanical locks prior to January 2, 2017:ALL PART NUMBERS BELOW DISCONTINUEDThe L-Series switched to a three-wire r...
Solenoid: Black (2 wires) Case side RX Normally Open: Green Normally Closed: Orange Cover side RX Normally Open: Gray Normally Closed: Red Common: Yellow
Refer to the MA RX diagram here for more information.