The DS is Dual Monitor Switch for Von Duprin 6000 series electric strikes.
DS option cannot be added to a Von Duprin 6000 series electric strikes in the field. It is only available factory inst...
The 5100 strike details are listed below:
Only operates with 12VDC or 24VDC power supply.
Will not operate with AC transformer.
12 or 24VAC can be converted to 12/24VDC using Von Duprin SO12 o...
The Von Duprin 6000 series electric strike can be converted by ordering the appropriate kits below. Kits include the solenoid, plunger, spring, and washer.
6000 Series solenoid Kit 12VDC -...
To convert the Von Duprin 6000 series electric strikes from FS to FSE or from FSE to FS follow these steps:
Remove the electric strike face plate.
Remove the strike b...
Part numbers:
FS slider, part # 090591 (Use for all EXCEPT 6211WF/6212WF/6221/6223. See 090798 below)
FS slider, part #090798 (Use this slider for FS models 6211W...
The Benchmark III control has a 24VDC, 2.5 amp power supply, and built in relay for controlling electric strikes or other accessories less than 2.5 amps current load.
For a fail secure strike, r...
The strike will always be DC. By using a SO24 or SO12(rectifiers) you will be able to convert the AC waveform from a transformer to a DC waveform that will be acceptable by the 6000 series strikes.
Von Duprin does not recommend using XP98/99 devices with any electric strike.
Von Duprin recommends using the standard 98/99 rim device. The XP device has 2000 pound holding forc...
Von Duprin 6223 electric strike is the most common closed back strike or the 6221 for open back strike on inactive leaf that can be used with Schlage L9000 or Von Duprin 7500 mortise lock.
Follow these questions to determine which Von Duprin electric strike model you have
1. What type of hardware is latching to the electric strike?
2. Single or pair ...
See Catalog to identify specific model: Von Duprin Electrical Security Products and Accessories Catalog
Von Duprin surface mounted 6300 electric strike paper template and installation instruction are provided with the electric strike. See attached
https://us.allegion.co...
Option boards are not required with PS900 series power supplies when using electric strikes. See the list of options below.
The PS902 would power up to 5 electric strikes at 24VDC or&n...
Make sure the proper power supply (PS873 or PS914) and proper gauge and run wire is used for Chexit devices shipped prior to 8-24-2015 with solenoid driven.
Related Solution: What wire&n...
The Schlage ES-6400 Electric Strike has been rebranded to Von Duprin 6400 Series Electric Strike, making Allegion’s full electric strike portfolio Von Duprin branded. All product featu...
Information available at: http://us.allegion.com/products/system_components/electric_strikes/pages/mortise_cylindrical.aspx
Overview, Features and Benefits, Technical Specifications, Wi...
Product Ordered after 7/10/2012 - Product identified by label on QEL motor
You no longer need to use the 900-2Q option board (no longer available) with the PS900 power supplies to ...
Product Ordered before 7/10/2012 - Product identified by no label on QEL motor.
You must use the 900-2Q option board with the PS900 power supplies to operate the QEL devices. The attached ta...
Inadequate power or wrong gauge wire is used the inrush current demand by CX will overload and shutdown the power supply. You must use the Von Duprin PS873 or newer PS914 supply.
Related soluti...
The 4600 Series operator has both a 12VDC and 24VDC output rated at 1A (combined load) to power strikes, maglocks, and other devices, but an EL device "always" has to have a separate PS914-2RS Seri...
The following application information apply to the 5100 electric strike:
Can only be used on a single door with a cylindrical lock
Can not be used on a pair of doors
Can not be used on a mullion
***The 6210 electric strike was designed to replace mechanical strikes in existing openings when access control is desired.***
Note: The Best 40H series lock is not listed on the 6210 electric s...
The 6111 electric strike can be used only on non rated openings less bottom rod with pullman top latch (use ES prefix when ordering device). Device back set will change to match the centerline of t...
The Von Duprin 6210 electric strike was designed for retrofit applications and will not work with the Falcon MA series lock when strike and lock body are mounted at standard locations (centerline o...
The Von Duprin 6111 electric strike would work with DOM 1790 device on medium style doors
Centerline of the 1790 device mounting screws are located 1 11/16" from face of stop. See d...
Electrical hinges or a power transfer units are the most commonly used practices to run electric power to locks and/or strikes.
Electric Hinges:
Most electric hinges will fit into...
The Von Duprin 6000 series electric strike has a 12 or 24VDC solenoid with plunger, spring and impact washer as shown 6000 solenoid
Make sure the solenoid spring and impact washer are not missin...
The Von Duprin electrified steel mullions, 4854 and 9854 come with a quick connector that connects the electric strike wires from the mullion to the frame through the top fitting. ...
The 22, 33/35A and 98/99 rim exit devices:
The 6111 is the most common electric strike to be used with these devices
6112 and 6113 electric strikes also could be used
The 6300 surface mount el...
Following information determine number of the Chexit devices that were shipped prior to 8-24-2015 from the factory with solenoid driven can be hooked up to a single Von Duprin PS873 or PS914 p...
Chexit devices shipped prior to 8-24-2015 with solenoid driven could cause the Von Duprin CX solenoid to pull and drop and sound the alarm with solid LED or no LED light after the rear...
This is not a recommended application as the electric strike does not have the same holding force as the XP98/99 rim exit device. The electric strike has 1500 pounds of holding force whereas the ...
The 4630/4630 operator has a 12 VDC and 24 VDC output that can power an electric strike or maglock. The wiring diagrams are shown on page 14 of the installation instructions (attached).
4600 Insta...
An electric strike or maglock (24 volt only) can be wired to a Senior Swing 2800/9500 series operator using the P10 Lock Interface cable.
To power the 24VDC electric strike or maglo...
The 8200 Series operator CANNOT power a strike, maglock, or EL device. A separate power supply is ALWAYS required. There is an onboard relay to control a strike, maglock, or EL device.
The 5100 electric strikes are for use with cylindrical locks only. Instead use the following:6211 electric strike is used with mortise lock without deadbolt on a new single door, hollow ...
You can't run 24VDC into the 12VDC electric strike, over voltage such as this will cause the solenoid to heat up and damage the solenoid. You must change to a 24V solenoid, part number 050240-00.