wiring for rxqel device

RELATED FAQS

Question
Answer
Use #18 gauge wire up to 200 feet maximum distance from PS900 x 900-2Q power supply to the QEL exit device. The new QEL+ no longer requires the 900-2Q board but still needs a different option board...
 EL devices are wired to the Senior Swing, using the P10 (761465) cable.  Connect the "GRAY" wire to the SC terminal on the 900-2RS card in the Von Duprin Power Supply and the "VIOLET" wire to the ...
For Product Shipped Prior to August 2012 using the old (black) potted module:a.       0-100 ft 14 gauge wireb.      0-200 ft 12 gauge wire&nbs...
Use a normally closed fire alarm as the input to the power supply option board (PS873-2 or PS914-2RS), this will hold the latch retracted.  During a fire alarm, the contact will open, dropping...
The 4600 Series operator has both a 12VDC and 24VDC output rated at 1A (combined load) to power strikes, maglocks, and other devices, but an EL device "always" has to have a separate PS914-2RS Seri...
To trigger two EL devices with one access input, wire your input into SC & I1, the first two screw terminals, then jump from I1 to I2 terminals.
The EL wiring adapter is not needed for QEL devices.
Partner Solution: Integrated Access Control Solution with AD-300 Hardwired, AD-400 Wireless Locks and Avigilon RedCloud Access Control System.See the download cut sheet at:Avigilon Red Cloud&n...
Applies to L9090EL/EU, L9091EL/EU, L9092EL/EU, L9093EL/EU, L9094EL/EU, L9095EL/EU The Schlage electrified L-Series wiring diagram can be found here and...
Applies to L9080EL/EU. L9082EL/EU (Discontinued) The Schlage electrified L-Series wiring diagram can be found here and the requirements are listed below.      ...
Click here to show the differences of an installed lockcase between the L9090, L9091, L9092, L9093, L9094, L9095 EL/EU and the L9080 EL/EU
Wiring and Riser diagrams can be accessed at:Common wiring diagrams can be accessed at:  http://kc.allegion.com/.   Click on the "Common Wiring Diagram" link.To request a custom wiri...
The Senior Swing control box has a built in (programmable) relay output for connection to a Fail Safe/Fail Secure electric strike/maglock or to an EL Device power supply.
The current (digital control box) activation input wiring harness (# 761464-00) is included in the Sr. Swing parts bag (-518), and has 4 wires in it, Black, White, Yellow, & Gray. This harness p...
Chexit devices shipped after 8-24-2015 with motor driven has a twelve wire connector wires and is keyed and can only plugged into the Chexit module in one direction.Chexit devices shipped...
The 8310-877 Bodyguard Safety Sensor attaches (plugs in) to the P1 connector on the Senior Swing controller. The 8310-846 (761462-00) wiring harness "included" with the 8310-877 safety sensor is us...
Chexit devices shipped after 8-24-2015 with motor driven:Use the Alarm Relay Contacts on Field Wiring Cable, blue and brown wires of the Chexit device.Connect the blue wire to +24VDC (red wire on F...
Chexit devices shipped prior to 8-24-2015 with solenoid driven:Use the external alarm contact, blue and brown wire on Chexit device.Connect the blue wire to the red wire and connect the brown wire ...
For Chexit devices shipped after 8-24-2015 with motor driven connect your normally closed contact from access control system between green and red on the twelve field wire ...
Chexit devices shipped prior to 8-24-2015 with solenoid driven could cause the Von Duprin CX solenoid to pull and drop and sound the alarm with solid LED or no LED light after the rear...
The EL Wiring Adapter is not needed for a CX device.
Some transformers in the power supplies provide a little humming noise and that is normal. If the humming in Von Duprin PS873 power supply is loud follow these steps. Remove the load from the outp...
The wires run through the device out to the EPT. See step 7 on page 5 of E996L instructions.
Product Ordered after 7/10/2012 - Product identified by label on QEL motor You no longer need to use the 900-2Q option board (no longer available) with the PS900 power supplies to ...
Product Ordered before 7/10/2012 - Product identified by no label on QEL motor. You must use the 900-2Q option board with the PS900 power supplies to operate the QEL devices.  The attached ta...
Since most wire transfer devices such as an EPT or electric hinges cannot provide large gauge wires, we take the small gauge wire into account when determining the overall wire size for the device....
For devices shipped after 8-24-2015 with motor driven:  a.       0-200 ft, use  #18 gauge wire b.      0-500 ft, use #14 gauge wir...
For Product Shipped prior to 8-24-2015 with solenoid driven:          a.       0-100 ft, use #14 Gauge Wire      b.&n...
Chexit devices shipped prior to 8-24-2015 with solenoid driven: A normally closed card reader contact, key pad contact or any other control contact connects to the Green an...
  For Product Shipped Prior to August 2012 using the old (black) potted module: a.       0-100 ft 14 gauge wire b.      0-200 ft 12...
 
Yes, the QEL device includes a cable assembly part number 110388-00.Since 12/2014, that cable comes in a package (part 116549) with the long cable mentioned above and the small cable that plug...
Chexit devices shipped after 8-24-2015 with motor driven:Attached is the installation instructions of the the Von Duprin Chexit devices that includes the wiring diagrams.Installation Instructions&n...
Chexit devices shipped before 8-24-2015 with solenoid driven:Attached are the single and double door wiring , cable voltage reading documents for trouble shooting, and the installation in...
Products shipped on or after August 8, 2012 no longer require the EL wiring adaptor. The ELK Wiring Adaptor (900ELK) was used only when using the PS914 power supply with either the 900-2RS or...